Oil-immersed transformers operate with inherent internal losses, and their economical and safe operation depends on mastering loss characteristics and promptly addressing faults. As a professional manufacturer and maintenance service provider, CHH Power has standardized processes for optimizing operational efficiency and resolving common issues—from loss-based economical operation to fault diagnosis (e.g., switch contact problems, short circuits) and cooling system maintenance. Below is a detailed breakdown of CHH Power’s technical practices.
1. Economical Operation of Oil-Immersed Transformers: Based on Loss Characteristics
Oil-immersed transformers have two main internal losses, and their balance determines the most economical operating state—a key focus of CHH Power’s operational guidance.
(1) Core Losses vs. Copper Losses
- Iron Loss (Core Loss): Caused by alternating magnetic flux in the iron core (hysteresis loss + eddy current loss). It is basically constant during operation, regardless of load changes (only related to input voltage and frequency).
- Copper Loss (Winding Loss): Caused by current flowing through the winding conductor (I²R loss). It changes with load—the higher the load current, the greater the copper loss.
(2) Most Economical Operating State
CHH Power’s engineering team confirms that the transformer operates most economically when:
- Iron loss = Copper loss (this state is called the “economic load rate,” typically 50–70% of the rated load).
- At this point, total loss (iron loss + copper loss) is minimized, and the transformer’s temperature rise stays within the normal range (≤65K for top oil temperature, per IEC standards)—avoiding overheating and extending service life.
(3) CHH Power’s Optimization Suggestion
For power utilities or industrial users, CHH Power recommends matching transformer capacity to actual load:
- Avoid long-term low-load operation (e.g., <30% rated load), which wastes energy due to high iron loss ratios.
- Avoid long-term overload operation (e.g., >120% rated load), which causes excessive copper loss and overheating.
2. Key Fault Diagnosis & Handling for Oil-Immersed Transformers
CHH Power uses a combination of on-site observations, instrument testing, and oil/gas analysis to diagnose and resolve common faults, ensuring minimal downtime.
(1) Fault 1: Poor Contact of Taps/Switches
- Diagnosis Method:
- Gas Relay Frequent Action: Poor contact causes local arcing, generating gas that triggers the gas relay (light gas alarm).
- Winding DC Resistance Measurement: Use a DC resistance tester to measure the resistance of each tap position. An abnormal resistance value (e.g., higher than the standard unbalance rate of ≤2%) indicates poor contact.
- CHH Power’s Handling Process:
- Power off the transformer and drain the insulating oil to expose the tap switch.
- Clean the contact surface (remove oxide or dirt) with fine sandpaper, then apply a thin layer of conductive grease (compatible with transformer oil) to reduce contact resistance.
- Reassemble, inject qualified insulating oil, and re-measure DC resistance to confirm the unbalance rate meets standards.
(2) Fault 2: Inter-Coil Short Circuit
- Diagnosis Method:
- Abnormal Internal Sound: A sharp “buzzing” or “crackling” sound (instead of the normal low hum) indicates arcing from short circuits.
- Gas Relay Frequent Action: Short circuits generate high temperatures, decomposing oil into gas (e.g., hydrogen) and triggering alarms.
- Bridge Measurement of Winding DC Resistance: A significant drop in DC resistance (e.g., >5% compared to historical data) confirms inter-coil short circuits.
- CHH Power’s Handling Process:
- Mild Short Circuit (Few Turns Affected):
- Open the tank, lift the winding, and reprocess the insulation between the shorted coils (use high-temperature epoxy resin to repair insulation layers).
- Severe Short Circuit (Multiple Turns Damaged):
- Replace the entire winding with CHH Power’s factory-manufactured windings (using the same material: oxygen-free copper wire + Class H insulation paper).
- Post-Repair Verification: Perform a low-voltage impulse test to confirm no residual short circuits, then inject oil and test dielectric strength.
- Mild Short Circuit (Few Turns Affected):
(3) Fault 3: Short Circuit Between Core Silicon Steel Plates
- Diagnosis Method:
- Abnormal Sound: A dull “humming” sound (caused by eddy current increase in the core).
- Insulation Resistance Drop: Measure the core-to-ground insulation resistance with a 2500V megohmmeter—values <100MΩ indicate possible short circuits.
- Oil & Gas Analysis: Short circuits cause local overheating, increasing dissolved gas in oil (e.g., methane, ethylene).
- Air Vibration Test: Tap the core lightly; uneven vibration suggests silicon steel sheet adhesion (short circuit).
- CHH Power’s Handling Process:
- Drain oil and open the tank to expose the core.
- Use a thin blade to separate the shorted silicon steel sheets, then apply a layer of core insulation paint (compatible with high temperatures) to restore insulation between sheets.
- Reassemble the core, retighten clamping devices, and re-measure core insulation resistance to ensure it meets standards.
3. Handling of Oil Shortage & Cooling System Faults
These two issues directly affect the transformer’s temperature control—CHH Power’s preventive maintenance ensures long-term stability.
(1) Oil Shortage Handling
- Problem Impact: Insufficient oil level exposes the winding to air, reducing insulation performance and increasing the risk of partial discharge.
- CHH Power’s Solution:
- Confirm the oil level (via the oil level gauge) and check for leaks (e.g., flange seals, valve connections) to avoid re-shortage.
- Add qualified insulating oil (same brand and type as the original oil) that has passed the dielectric strength test (≥35kV/2.5mm) and moisture test (≤15ppm).
- Add oil to the “normal” oil level mark (corresponding to ambient temperature), then run the transformer at 50% load for 2 hours to ensure oil circulation.
(2) Cooling System Fault Handling
Cooling system failures cause oil temperature rise—CHH Power focuses on two common scenarios:
| Fault Type | CHH Power’s Diagnosis & Handling |
|---|---|
| Radiator Blockage | – Symptom: Top oil temperature exceeds 70°C (normal ≤65K rise). |
| Forced Oil Circulation (FOC) Heat Exchanger Blockage | – Symptom: Oil temperature rises rapidly even with fans/pumps running. |
- Additional Note: For indoor oil-immersed transformers, ensure the inlet/outlet of the transformer room is unobstructed. Clean accumulated dust monthly to maintain air circulation—blocked vents can increase indoor temperature by 5–10°C, indirectly raising oil temperature.
CHH Power emphasizes that regular preventive maintenance (e.g., quarterly oil testing, semi-annual cooling system inspection) is more effective than post-fault repair. By mastering loss characteristics and standardizing fault handling, oil-immersed transformers can maintain safe, economical operation for 20+ years.















































