
Power Transformer Fault: Oil Leakage from Cast Iron Components
Root Causes of Cast Iron Oil Leakage (Power Transformer Fault)
- Sand Holes: These are tiny cavities formed during the casting process when molten iron traps air or sand particles. Often invisible to the naked eye, sand holes remain dormant until oil pressure or thermal expansion creates a pathway for seepage. This power transformer fault is particularly common in older transformers or those manufactured with subpar casting standards.
- Cracks: Cracks in cast iron components are a more severe form of this power transformer fault. They typically develop due to thermal stress (from repeated heating and cooling cycles), mechanical impact (such as accidental bumps during maintenance), or age-related material fatigue. Even small cracks can widen over time, leading to significant oil loss.
Step-by-Step Diagnosis and Repair for This Power Transformer Fault
Step | Action | Purpose | Pro Tips for Effective Execution |
|---|---|---|---|
1 | Isolate the Transformer and Locate the Leak | Ensure safety and pinpoint the exact source of the power transformer fault | Shut off power and allow the transformer to cool. Use a UV dye test kit (add dye to the oil, wait 24 hours, and use a UV light to detect leaks) for hard-to-find sand holes. |
2 | Prepare the Surface | Remove oil residue, rust, and debris to ensure proper sealant adhesion | Use acetone or a transformer-specific degreaser. For rusted areas, lightly sand the surface to expose clean metal—avoid over-sanding, which can widen cracks. |
3 | Drill Relief Holes (for Cracks) | Prevent crack propagation during repair | Drill a 2-3mm hole at both ends of the crack. This relieves stress and stops the crack from spreading when sealant is applied. |
4 | Apply High-Quality Sealant | Fill sand holes or cracks with a durable, oil-resistant material | Choose a two-part epoxy sealant rated for transformer oil and high temperatures (e.g., -40°C to 150°C). Apply in thin, even layers, ensuring full coverage of the fault area. |
5 | Cure and Test | Verify the repair’s effectiveness and prevent future leakage | Allow the sealant to cure for the manufacturer’s recommended time (typically 24-48 hours). Conduct a pressure test (3-5 psi above operating pressure) and monitor for 48 hours to ensure no re-leakage. |
Real-World Case Study: Resolving a Persistent Cast Iron Leak Power Transformer Fault

Preventive Measures for Cast Iron Leak Power Transformer Fault
- Conduct quarterly visual inspections of cast iron components for rust, discoloration, or early leakage signs.
- Apply a corrosion-resistant coating to cast iron surfaces every 2-3 years, especially for outdoor transformers.
- Monitor oil pressure and temperature regularly—sudden changes can indicate stress on cast iron components.
- Avoid mechanical impact during maintenance; use proper lifting equipment when working near the transformer tank.
Power Transformer Fault: Radiator Oil Leakage
Why Radiator Leakage Occurs (Power Transformer Fault Root Causes)
- Residual Stress from Manufacturing: Stamping and welding processes during radiator production can leave residual stress in heat pipes or fins. Over time, thermal cycling (heating and cooling) causes this stress to manifest as cracks or weld failures—one of the most common root causes of this power transformer fault.
- Thermal Fatigue: Transformers in industrial settings often experience frequent load changes, leading to repeated expansion and contraction of radiator components. This fatigue weakens metal joints, resulting in leakage.
- Corrosion: Outdoor transformers are vulnerable to corrosion from rain, humidity, or industrial pollutants. Corrosion eats away at metal surfaces, creating holes and weakening welds.
- Physical Damage: Debris, falling objects, or accidental impacts during maintenance can damage radiator fins or pipes, causing immediate leakage.

Diagnosing and Repairing Radiator Oil Leakage Power Transformer Fault
- Isolate the Radiator: First, shut off the transformer and close the radiator valves to prevent further oil loss. This step is critical to avoid worsening the power transformer fault and to ensure safe repair conditions.
- Locate the Leak: For visible leaks, use a dry cloth to wipe the radiator—oil stains will highlight the fault area. For hidden leaks, use a pressure test (apply 2-3 psi to the radiator) or a gas leak detector (e.g., helium) for precision.
- Choose the Appropriate Repair Technique: The repair method depends on the leak’s size and location:
- Epoxy Injection: Ideal for small, hard-to-reach leaks (e.g., in heat pipes). Use a specialized epoxy injector to fill the leak from the inside, ensuring full coverage.
- Welding Repairs: For larger cracks or weld failures, welding is necessary. Only certified welders with transformer repair experience should perform this work—poor welding can cause further damage.
- Composite Wraps: For external pipe leaks, use a fiberglass composite wrap soaked in epoxy. This provides both sealing and structural reinforcement, ideal for corroded areas.
- Flush the Radiator: After repair, flush the radiator with transformer oil to remove debris or sealant residue. This prevents clogging, which can lead to a secondary power transformer fault (overheating).
- Test Cooling Efficiency: Reconnect the radiator, refill with oil, and power on the transformer. Monitor temperature levels for 72 hours to ensure the cooling system is functioning properly.
Case Study: Cost-Effective Resolution of Multiple Radiator Leaks
Preventing Radiator Leak Power Transformer Fault
- Clean radiators quarterly to remove dust, debris, and industrial pollutants—clogged fins increase thermal stress.
- Inspect welds and pipe joints annually for signs of corrosion or cracking.
- For outdoor transformers, install weather shields to protect radiators from rain, snow, and UV damage.
- Monitor load changes—avoid sudden, frequent overloads that cause extreme thermal cycling.
Power Transformer Fault: Leakage from Porcelain Vases and Glass Oil Labels

Causes of Porcelain and Glass Leak Power Transformer Fault
- Thermal Expansion and Contraction: Porcelain and glass have different thermal expansion rates than metal flanges. Repeated heating and cooling cycles cause seals to degrade over time, creating gaps for oil leakage.
- Improper Installation: Over-tightening or under-tightening bolts during installation can damage seals or create uneven pressure, leading to this power transformer fault.
- Vibration: Operational vibrations (from nearby machinery or transformer load changes) can loosen seals or crack porcelain/glass components.
- Age-Related Degradation: Seals made of rubber or cork degrade over time, losing elasticity and effectiveness. Older transformers are particularly vulnerable to this power transformer fault.
Repair Strategies for Porcelain and Glass Leak Power Transformer Fault
- Isolate and Inspect: Shut off the transformer and allow it to cool. Inspect the porcelain/glass component and surrounding seals for cracks, damage, or degradation. For glass oil labels, check if the glass is cracked or the seal is brittle.
- Remove Old Seals: Carefully remove the old seal using a plastic scraper (avoid metal tools that can scratch porcelain/glass). Clean the surface with acetone to remove oil residue and debris.
- Choose the Right Sealing Material: Select a material compatible with transformer oil, temperature fluctuations, and the component’s material:
- Polymer Composites: Ideal for porcelain bushings—flexible, durable, and resistant to oil and temperature changes.
- Silicone Sealants: Best for glass oil labels—flexible enough to accommodate thermal expansion and contraction.
- Epoxy Resins: Use for small cracks in porcelain (avoid using on glass, as epoxy is too rigid).
- Apply the Sealant: Apply a thin, even layer of sealant to the seal groove. For porcelain bushings, ensure the sealant covers the entire interface between porcelain and metal. For glass oil labels, apply sealant around the glass edge.
- Cure and Test: Allow the sealant to cure fully (follow manufacturer’s instructions). Conduct a pressure test (1-2 psi) and monitor for 24 hours to ensure no leakage. For porcelain bushings, also test insulation resistance with a megohmmeter to ensure no damage to insulation.
Case Study: Resolving Persistent Bushing Leaks

Power Transformer Fault: Proactive Prevention and Long-Term Reliability
Comprehensive Preventive Maintenance Schedule for Power Transformer Fault Avoidance
Maintenance Task | Frequency | Purpose |
|---|---|---|
Visual Inspections for Leaks, Rust, or Damage | Monthly | Early detection of power transformer fault signs |
Oil Quality Testing (Dielectric Strength, Moisture, Acidity) | Annually | Monitor oil condition—degraded oil accelerates seal failure |
Seal Inspection and Replacement (if needed) | Bi-annually | Prevent seal degradation-related power transformer faults |
Thermal Imaging of Components | Quarterly | Detect hot spots indicating stress or early fault signs |
Pressure Testing of Tank and Radiators | Bi-annually | Verify structural integrity and prevent leakage |
Dissolved Gas Analysis (DGA) of Oil | Quarterly (for critical transformers) | Detect internal power transformer faults (e.g., arcing, overheating) before they cause leakage |
Key Best Practices for Power Transformer Fault Prevention
- Use High-Quality Materials: Invest in premium seals, gaskets, and sealants designed for transformer applications. Cheap materials degrade quickly, leading to power transformer faults.
- Proper Installation: Ensure all components are installed by certified technicians. Follow manufacturer guidelines for torque specifications and seal application.
- Environmental Controls: For indoor transformers, maintain stable temperature and humidity levels. For outdoor units, use protective enclosures to shield against harsh weather.
- Vibration Management: Install vibration dampeners if the transformer is near heavy machinery. Tighten mounting bolts regularly to prevent vibration-related seal damage.
- Training and Documentation: Train maintenance staff to recognize early power transformer fault signs. Keep detailed records of repairs, inspections, and oil test results for future reference.
Power Transformer Fault: When to Repair vs. Replace Components
Component | Repair When | Replace When |
|---|---|---|
Cast Iron Components | Minor cracks, small sand holes, or localized corrosion | Extensive corrosion, large cracks (over 10cm), or multiple recurring leaks |
Radiators | Small leaks, isolated corrosion spots, or minor fin damage | Multiple leaks, severe corrosion affecting >30% of the radiator, or damaged heat pipes |
Porcelain Bushings | Seal degradation, minor surface irregularities | Cracks in porcelain, severe oil leakage, or insulation failure |
Glass Oil Labels | Seal failure (glass intact) | Cracked or broken glass |
Seals/Gaskets | Minor degradation (no visible cracks) | Brittleness, cracks, or repeated failure |
Cost-Benefit Consideration for Power Transformer Fault Resolution

Conclusion: Mastering Power Transformer Fault Resolution for Long-Term Reliability
FAQ About Power Transformer Fault
What are the common types of power transformer faults and their main hazards?
Power transformer faults are mainly categorized into insulation faults, partial discharge faults, and overheating faults. Insulation faults, including insulation paper aging, insulation oil deterioration, and insulation breakdown, are mostly caused by long-term high-temperature operation, which decomposes insulation materials and produces characteristic gases like methane and ethylene, potentially leading to winding short circuits and equipment burnout. Partial discharge faults, triggered by air gaps, impurities in insulation, or electric field concentration at electrode tips, account for approximately 30% of major transformer failures as they accelerate insulation aging. Overheating faults, with the highest proportion from poor contact of tap changers, cause abnormal increases in acetylene and hydrogen content in oil, and severe cases may result in fires or explosions. A 2022 power grid incident in a certain region, caused by undetected tap changer overheating, led to 12 hours of equipment outage, affecting 50,000 households and resulting in direct economic losses exceeding 2 million yuan.
How does Dissolved Gas Analysis (DGA) diagnose power transformer faults?
Dissolved Gas Analysis (DGA) is a widely used diagnostic method based on the principle that insulation materials decompose to produce characteristic gases when faults occur, with specific gas types corresponding to fault types. For example, partial discharge generates a large amount of hydrogen and methane, high-temperature overheating produces ethylene and ethane, and arc discharge leads to high concentrations of acetylene. By detecting the content and ratio of gases such as hydrogen, methane, ethane, ethylene, and acetylene in oil using gas chromatographs, fault types can be judged using the IEC-recommended three-ratio method or Rogers method. DGA is simple to operate and low-cost, enabling early detection of internal faults. A power grid company once detected a gradual increase in acetylene content in a 220kV transformer 6 months in advance through regular DGA testing, confirming local winding insulation overheating and avoiding fault expansion.
What are the advantages of partial discharge detection technology in transformer fault location?
Partial discharge detection identifies faults by collecting electrical or ultrasonic signals generated by internal partial discharges through sensors, with common methods including the pulse current method, the ultra-high frequency (UHF) method, and the ultrasonic method. The UHF method, in particular, has strong anti-interference ability as it captures ultra-high frequency electromagnetic waves from partial discharges, achieving fault location accuracy within 10cm, which is suitable for fault troubleshooting. In 2023, a substation successfully located an air gap discharge fault inside the winding insulation of a transformer using UHF partial discharge detection, providing precise guidance for maintenance.
How does infrared thermal imaging technology help detect power transformer faults?
Infrared thermal imaging diagnosis identifies abnormal temperature areas by capturing the surface temperature field distribution of transformers using infrared thermal imagers, based on the characteristic that fault locations have abnormal temperature rises. This method allows live detection without a power outage and intuitively displays fault positions, making it suitable for detecting overheating faults caused by poor tap changer contact or multi-point core grounding. During the high-temperature summer load period, operation and maintenance personnel once found that the temperature of a transformer bushing joint reached 85℃ (normal temperature should be below 65℃) through infrared thermal imaging, and timely handled the loose joint to avoid overheating damage. However, it is greatly affected by ambient temperature and equipment surface contamination, and cannot detect deep internal faults, requiring collaboration with other methods.
What is the role of artificial intelligence in power transformer fault diagnosis?
With the development of artificial intelligence, machine learning, and deep learning, integrated diagnostic methods have become a new direction. By collecting a large amount of transformer fault sample data (including DGA data, partial discharge signals, temperature data, etc.), models such as neural networks, support vector machines (SVM), or random forests are trained to achieve multi-feature integrated diagnosis. A research team’s three-feature integrated diagnosis model combining DGA, partial discharge, and infrared temperature achieved a diagnostic accuracy of 94.7% and an early minor fault recognition rate of 88% in 1000 fault sample tests, significantly higher than traditional methods. AI diagnosis can process complex multi-dimensional data, reduce reliance on manual experience, and optimize models by supplementing sample data.
What are the main causes of transformer winding faults?
Common winding faults include short circuits and open circuits. Short circuits can be caused by copper or aluminum wire breakage due to long-term overload leading to excessive conductor temperature, fatigue fracture from mechanical vibration, insulation aging from oil impurities and moisture, or manufacturing defects such as uneven wire crimping. Open circuits are often due to loose or broken winding leads from corroded fasteners or mechanical damage during transportation, or circuit interruption from insulation damage. These faults may result in sudden loud noises, abnormal current fluctuations, or even transformer failure to transmit electrical energy normally.
How to handle transformer core faults?
Core faults mainly include local core welding and core loosening or displacement. Local core welding is caused by poor insulation between core laminations or over-excitation during operation, leading to abnormal increases in no-load current and excessive acetylene content in oil. The treatment involves disassembling the core to check insulation thickness, removing sludge, and re-spraying insulating paint. Core loosening or displacement is often due to insufficient pre-tightening force of foundation bolts or worn clamping devices, resulting in operational noise and rust. Solutions include reinforcing bolts, replacing worn parts, and installing damping devices. For multi-point core grounding, insulation measures should be taken to eliminate the fault.
What are the common faults of transformer cooling systems and their solutions?
Common cooling system faults include oil circuit blockage and oil pump failure. Oil circuit blockage is caused by sludge deposition from long-term operation or dirty cooler filters, leading to decreased cooling efficiency and abnormal fan motor current. The solution involves cleaning or replacing filters and using ultrasonic cleaners to remove sludge. Oil pump failures, such as motor overload shutdown or mechanical wear leakage, require checking the motor and transmission mechanism, and replacing damaged components if necessary. Regular visual inspections and differential pressure monitoring of filters are recommended to prevent such faults.
How to prevent insulation faults in power transformers?
Preventing insulation faults requires multiple measures. Regular oil quality testing is essential, including semi-annual moisture content detection (should be less than 5ppm) and evaluation of antioxidant performance. Avoiding long-term full-load operation (recommended load rate below 80%) and using frequency conversion startup to reduce inrush current can reduce insulation damage. Maintaining the operating environment with humidity below 80% and avoiding direct sunlight on the oil tank prevents insulation aging. Additionally, regular replacement of insulating oil and inspection of insulation paper status are necessary; severely aged insulation paper should be replaced promptly. Installing online monitoring systems to track insulation performance in real-time also helps prevent faults.
What are the hazards of transformer tap changer faults, and how to resolved?
Tap changer faults, such as poor contact and inaccurate tap positions, have significant impacts. Poor contact increases contact resistance, causing local overheating, while inaccurate positions lead to abnormal output voltage, affecting power system operation. Resolutions include cleaning, adjusting, and overhauling the tap changer to ensure good contact, and recalibrating positions with testing and verification. Regular inspections of tap changer operation status and lubrication maintenance are recommended to prevent faults.
What is the impact of power transformer faults on the power grid?
Power transformers are core power system equipment, and their faults directly affect the stability and safety of the power supply. Minor faults may cause voltage fluctuations and load interruptions, while major faults can lead to large-scale power outages, affecting residential and industrial electricity use. For example, a 2022 transformer fault caused a 12-hour outage affecting 50,000 households. Additionally, faults may damage other power grid equipment, trigger cascading failures, and result in huge economic losses. Ensuring stable transformer operation is therefore crucial for maintaining power grid reliability.
What are the limitations of DGA in transformer fault diagnosis, and how to overcome?
Although DGA is widely used, it has limitations: it cannot accurately locate fault positions, and gas ratios may overlap when multiple faults coexist, leading to misdiagnosis. To overcome these, online DGA monitoring technology can be adopted to collect gas data in real-time, dynamically tracking concentration trends and reducing time lag from offline testing. Combining DGA with other methods, such as partial discharge detection and infrared thermal imaging, achieves multi-method integrated diagnosis, significantly improving diagnostic accuracy. For example, integrating DGA with BP neural networks increases fault recognition accuracy to over 94%, an improvement of 15%-20% compared to single methods.
How to formulate a preventive maintenance plan for power transformers?
Formulating a preventive maintenance plan requires systematic management. Regular inspection points include monthly recording of oil level and color changes, and checking for bushing cracks or discharge traces. Establishing a fault database to record fault types and frequencies, and analyzing common issues in similar equipment, provides a basis for maintenance. Maintenance plans should be developed based on operating years (e.g., annual overhauls for transformers over 10 years old) and DGA trend predictions of potential faults. Additionally, optimizing load management and environmental control, such as avoiding long-term overload and maintaining a dry environment, is part of preventive maintenance.
What are the key indicators for transformer fault diagnosis using electrical testing?
Electrical testing indicators for transformer fault diagnosis include no-load loss (reference value: 0.1%-0.2% of rated capacity), no-load current waveform, short-circuit impedance (reference range: 4%-10%), turns ratio (error allowed ±0.2%), and insulation resistance (reference value: above 20MΩ). Abnormal no-load loss and current indicate potential winding or core faults; deviations in short-circuit impedance reflect winding structural changes; turns ratio errors may signal 匝间 short circuits or incorrect tap positions; and low insulation resistance indicates damp or aged insulation. These indicators comprehensively reflect transformer operational status.
How does machine learning optimize transformer fault prediction?
Recent studies have leveraged DGA data with AI-driven techniques to enhance predictive performance. A novel machine learning framework integrating Histogram Gradient Boosting (HGB) with Particle Swarm Optimization (PSO) for hyperparameter tuning achieves high robustness. Experimental results show the hybrid HGB-PSO model reaches 97.85% accuracy, 98.90% precision, 97.33% recall, and 98.99% F1-score. Compared to traditional ratio-based methods (e.g., IEC ratio method, Roger’s ratio method), machine learning models better handle complex data, improve diagnostic precision, and reduce reliance on manual interpretation, making them suitable for large-scale transformer fault prediction.
What are the emergency handling procedures for power transformer faults?
Emergency handling of transformer faults includes power outage isolation and preliminary investigation. First, start the backup transformer and confirm the circuit breaker open state to ensure safe isolation. Then, conduct a preliminary inspection: check oil level, color, and temperature; assess for abnormal noises or discharge sounds. For different fault types, take targeted measures: immediately shut down for winding short circuits to inspect damage; use DGA to locate insulation fault points; and eliminate multi-point grounding for core faults. Timely and standardized emergency handling minimizes fault expansion and reduces economic losses.
What factors affect the accuracy of transformer fault diagnosis?
Several factors affect diagnostic accuracy, including environmental conditions (ambient temperature, humidity, and dust interfere with infrared thermal imaging and partial discharge detection), fault complexity (multiple concurrent faults cause overlapping characteristic signals), sensor performance (insensitive sensors miss early fault signals), and data quality (insufficient or inaccurate sample data affects AI model training). To improve accuracy, it is necessary to select appropriate diagnostic methods based on on-site conditions, use high-sensitivity sensors, and establish a comprehensive fault sample database.
How to repair transformer winding faults?
Winding fault repair depends on fault severity. For minor 匝间 short circuits, local repairs such as replacing damaged winding sections or applying DC withstand voltage to eliminate defects can be performed. Severe short circuits or open circuits require finding the fault point (e.g., broken wires or poor connections) for re-welding or reconnection; in serious cases, the entire winding must be replaced or the transformer overhauled. During repair, ensuring winding insulation performance is critical, such as using vacuum impregnation technology to enhance voltage resistance after insulation repair. Post-repair testing (e.g., DC resistance and turns ratio measurements) verifies repair quality.
What are the latest advancements in transformer fault detection sensors?
Recent advancements in fault detection sensors focus on improving sensitivity and real-time performance. For DGA, more sensitive gas sensors enable the detection of trace characteristic gases, facilitating early fault identification. UHF sensors for partial discharge detection have enhanced anti-interference capabilities, improving fault location accuracy. Additionally, fiber optic temperature sensors, resistant to electromagnetic interference, accurately measure winding and core temperatures in real-time. These advanced sensors provide more reliable data support for integrated diagnosis, enabling early fault warning and improving transformer operational reliability.
What are the global trends in power transformer fault statistics and analysis?
Global transformer fault statistics show that insulation aging, overheating, and tap changer issues are the most common fault causes, with a higher fault rate in transformers over 10 years old. Analysis trends focus on big data and IoT integration, establishing global transformer fault databases to identify common failure modes and risk factors. Predictive maintenance based on real-time monitoring data is increasingly adopted to replace traditional scheduled maintenance, reducing unplanned outages. Additionally, research on low-carbon and environmentally friendly insulation materials aims to improve transformer durability and reduce fault rates, aligning with global energy conservation and emission reduction goals.
